82 ACS 300 User’s Manual
Chapter 8 - Fault Tracing
Note! If the fault persists, contact the nearest ACS 300 supplier.
THE DRIVE DOES NOT
FUNCTION
CORRECTLY IN
REMOTE CONTROL
CHECK:
the polarity of the signals
the position of switch S1
the position of jumper X5
CONTROL PANEL Processor incompatible with
Control Panel.
Check the connection between
the processor and the panel.
Control card error Contact your nearest ACS 300
supplier.
WRITE -> ACS ERROR
VERSION MISMATCH
Mismatch of ACS 300 software.
Note! Parameter copying
unsuccessful.
Set the parameters manually.
OUTPUT FREQUENCY
< REFERENCE
FREQUENCY
wrong parameter values
too much load
wrong motor connection
CHECK:
supply voltage (400 V series)
I LIMIT high enough
IR COMP not too high
motor connection Star/Delta
ACS 300 sizing with respect to
the load
Fault indication Possible cause Remedy