20 ACS 300 User’s Manual
Chapter 3 - Power Connections
Table 3-1 Cables and fuse recommendations, 200-240 V.
Table 3-2 Cables and fuse recommendations, 380-480 V.
Type
designation
208-240 V
Rated input
current
I
1
[A]
Recommended
input fuse
[A]
Recommended mains
and motor cable [mm
2
]
1
phase
3
phase
1
phase
3
phase
1-phase 3-phase
ACS 311-1P1-1 6.6 - 10 - 21.5+1.5 31.5+1.5
ACS 311-1P6-1 8.9 - 10 - 21.5+1.5 31.5+1.5
ACS 301-2P1-1 12.2 - 16 10 22.5+2.5 31.5+1.5
ACS 311-2P1-1 12.2 8.4 16 10 22.5+2.5 31.5+1.5
ACS 301-2P7-1 15.7 - 16 10 22.5+2.5 31.5+1.5
ACS 311-2P7-1 15.7 9.8 16 10 22.5+2.5 31.5+1.5
ACS 301-4P1-1 22.4 - 32 16 26+6 31.5+1.5
ACS 311-4P1-1 22.4 12.9 32 16 26+6 32.5+2.5
ACS 3_1-4P9-1 - 10.6 - 16 - 36+6
ACS 3_1-6P6-1 - 14.4 - 16 - 36+6
ACS 3_1-8P7-1 - 21.0 - 25 - 310+10
Type designation
380-480 V
Rated input
current
I
1
[A]
Recommended
input fuse
[A]
Recommended
mains and motor
cable [mm
2
]
3 phase 3 phase 3 phase
ACS 3_1-1P6-3 3.0 10 31.5+1.5
ACS 3_1-2P1-3 3.9 10 31.5+1.5
ACS 3_1-2P7-3 5.0 10 31.5+1.5
ACS 3_1-4P1-3 7.5 16 32.5+2.5
ACS 3_1-4P9-3 9.1 16 32.5+2.5
ACS 3_1-6P6-3 12.1 16 32.5+2.5
ACS 3_1-8P7-3 10.6 16 36+6
ACS 3_1-012-3 14.4 16 36+6
ACS 3_1-016-3 21 25 310+10