26 ACS 300 User’s Manual
Chapter 4 - Control Connections
Relay Outputs
First relay output on terminals X1:13, X1:14 and X1:15.
Second relay output on terminals X1:16, X1:17 and X1:18.
When relay 1 is de-energised, there is continuity between
terminals X1:13 and X1:14. Relay 1 is de-energised, if the
ACS 300 is not connected to the mains. When relay 1 is
energised, there is continuity between terminals X1:14 and
X1:15.
Relay 2 is similar to relay 1 and the corresponding terminals are
X1:16, X1:17 and X1:18.
The information indicated with relay outputs can be selected.
Refer to Chapter 7 page 67 for further information.
Relay 1 output
Relay 2 output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
REF
GND
AI+
GND
+24 V
DI1
DI2
DI3
DI4
DI5
AO+
GND
RO 11
RO 12
RO 13
RO 21
RO 22
RO 23
Terminal
block X1
Standard
Start/Stop
Reverse
Constant speed
Constant speed
ACC2/DEC2
3-wire
Start
Stop
Reverse
Constant speed
Constant speed
Motor
Potentio-meter
Start
Reverse
Increment frequency
Decrement frequency
Constant speed
OFF ON
0 1
0 1
OFF ON
0 1
OFF ON
Alternate
Start forward
Start reverse
Constant speed
Constant speed
ACC2/DEC2
OFF ON
0 1
Param set 2
Param set 2
Param set 2
Param set 2
DI 5