Start-up and control with I/O 19
5. Start-up and control with I/O
How to start up the drive
WARNING! The start-up may only be carried out by a qualified
electrician.
The safety instructions given in chapter Safety on page 5 must be followed during the
start-up procedure.
The drive will start up automatically at power up if the external run command is on
and the drive is in the remote control mode.
Check that the starting of the motor does not cause any danger. De-couple the
driven machine if there is a risk of damage in case of incorrect direction of rotation.
Note: By default, parameter 1611 PARAMETER VIEW is set to 2 (SHORT VIEW),
and you cannot see all actual signals and parameters. To be able to view them, set
parameter 1611 PARAMETER VIEW to 3 (LONG VIEW).
ī Check the installation. See the checklist in section Installation checklist on page
18.
How you start up the drive depends on the control panel you have.
ī If you have a Basic Control Panel, follow the instructions given in section How
to perform a manual start-up on page 20.
ī If you have an Assistant Control Panel, you can either run the Start-up
assistant (see section How to perform a guided start-up on page 23) or perform a
manual start-up (see section How to perform a manual start-up on page 20).
The Start-up assistant, which is included in the Assistant Control Panel only,
guides you through all essential settings to be done. In the manual start-up, the
drive gives no guidance; you go through the very basic settings by following the
instructions given in section How to perform a manual start-up on page 20.