Start-up and control with I/O 21
motor nominal voltage (parameter 9905)
Setting of parameter 9905 is shown below as an
example of parameter setting with the Basic Control
Panel. You find more detailed instructions in chapter
Control panels, section Basic Control Panel in ACS310
Users Manual (3AUA0000044201 [English]).
1. To go to the Main menu, press if the bottom
line shows OUTPUT; otherwise press
repeatedly until you see MENU at the bottom.
2. Press keys / until you see PAr, and
press .
3. Find the appropriate parameter group with keys
/ and press .
4. Find the appropriate parameter in the group with
keys / .
5. Press and hold for about two seconds until the
parameter value is shown with under the value.
6. Change the value with keys / . The value
changes faster while you keep the key pressed
down.
7. Save the parameter value by pressing .
Enter the rest of the motor data:
motor nominal current (parameter 9906)
Allowed range: 0.22.0 · I
2N
A
motor nominal frequency (parameter 9907)
motor nominal speed (parameter 9908)
motor nominal power (parameter 9909)
Select the application macro (parameter 9902)
according to how the control cables are
connected. The default value 1 (ABB
STANDARD) is suitable in most cases.