28 Actual signals and parameters in the short view
Default values with different macros
When application macro is changed (9902 APPLIC MACRO), the software updates
the parameter values to their default values. The table below shows the parameter
default values for different macros. For other parameters, the default values are the
same for all macros. See the parameter list starting on page 29 in this manual and
chapter Actual signals and parameters in ACS310 Users Manual (3AUA0000044201
[English]). For information on the different macros, see chapter Application macros in
the same manual.
Index Name/Selecti
on
ABB
STANDARD
3-WIRE ALTERNA
TE
MOTOR
POT
HAND/AU
TO
PID
CONTROL
PFC
CONTROL
SPFC
CONTROL
9902 APPLIC
MACRO
1 = ABB
STANDAR
D
2 = 3-
WIRE
3 = ALTER
NATE
4 = MOTO
R POT
5 =
HAND/AU
TO
6 = PID
CONTROL
7 = PFC
CONTROL
15 = SPFC
CONTROL
1001 EXT1
COMMANDS
DI1,2 DI1P,2P,3 DI1F,2R DI1,2 DI1,2 DI1 DI1 DI1
1002 EXT2
COMMANDS
NOT SEL NOT SEL NOT SEL NOT SEL DI5,4 DI5 DI5 DI5
1003 DIRECTION REQUEST REQUEST REQUEST REQUEST REQUEST FORWARD FORWARD FORWARD
1102 EXT1/EXT2
SEL
EXT1 EXT1 EXT1 EXT1 DI3 DI2 DI2 DI2
1103 REF1
SELECT
AI1 AI1 AI1 DI3U,
4D(NC)
AI1 AI1 AI1 AI1
1106 REF2
SELECT
AI2 AI2 AI2 AI2 AI2 PID1OUT PID1OUT PID1OUT
1201 CONST
SPEED SEL
DI3,4 DI4,5 DI3,4 DI5 NOT SEL DI3 NOT SEL NOT SEL
1304 MINIMUM AI2 1.0% 1.0% 1.0% 1.0% 20.0% 20.0% 20.0% 20.0%
1401 RELAY
OUTPUT 1
FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) PFC PFC
1601 RUN ENABLE NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL DI4 NOT SEL NOT SEL
1805 DO SIGNAL FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) FAULT(-1) PFC
2008 MAXIMUM
FREQ
50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0Hz 52.0 Hz 52.0 Hz
2201 ACC/DEC 1/2
SEL
DI5 NOT SEL DI5 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
2202 ACCELER
TIME 1
5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 30.0 s
2203 DECELER
TIME 1
5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 5.0 s 30.0 s
3019 COMM FAULT
TIME
3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 10.0 s
4001 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5 2.5
4002 INTEGRATION
TIME
60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s 3.0 s
4101 GAIN 1.0 1.0 1.0 1.0 1.0 1.0 2.5 2.5
4102 INTEGRATION
TIME
60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 3.0 s 3.0 s
8116 AUX MOT
STOP D
3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 20.0 s
8118 AUTOCHNG
INTERV
NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL 0.1 h
8123 PFC ENABLE NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL ACTIVE SPFC
ACTIVE