EasyManua.ls Logo

ABB ACS800 Series - Cabinet Installation (IP21, UL Type 1); Frame Size R5

ABB ACS800 Series
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
70
Cabinet installation (IP21, UL type 1)
The drive can be installed in a cabinet without the connection box and front cover.
It is recommended:
to ground the cable shield 360 degrees at the cabinet entry
to lead the cable unstripped as close to the terminals as possible.
Secure the cables mechanically.
Protect the RMIO board terminals X25 to X27 against contact when input voltage
exceeds 50 V AC.
Frame size R5
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud.
2. Press the shroud onto the terminals.
Removal of the shroud with a screw driver:
1
2
2

Table of Contents

Other manuals for ABB ACS800 Series

Related product manuals