8 Quick Start-up Guide for ACS850 with Standard Control Program
Select the motor control mode. DTC is suitable for
most cases.
Scalar mode is recommended if
the nominal current of the motor is less than 1/6
of the nominal current of the drive,
the drive is used for test purposes with no motor
connected, or
the drive controls multiple motors and the number
of motors connected is variable.
99.05 Motor ctrl mode
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
Permanent magnet motor nameplate example:
Note: Set the motor data to
exactly the same value as on the
motor nameplate. For example, if
the motor nominal speed is 1470
rpm on the nameplate, setting the
value of parameter 99.09 Mot
nom speed to 1500 rpm results in
incorrect operation of the drive.
If D (delta) data is chosen, then
connect the motor in delta.
If Y (star) data is selected, then
connect the motor in star.
motor nominal current
Allowed range: approximately 1/6 × I
2n
… 2 × I
2n
of
the drive (0…2 × I
2nd
if parameter 99.05 Motor ctrl
mode = Scalar).
99.06 Mot nom current
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
3 ~ motor M2BJ 280SMB 10 B3
No 3424522
A
BB Motors
Ins.cl. F IP 55
V
400 D
Hz
50
kW
55
r/min
600
A
103
cos
M
0.97
IA/IN
t
E/s
Prod. code 2GBJ285220-ADA405445477
6316/C3
6316/C3
630kg
IEC 34-1
S1 SPEC INSUL.
JK-21640-1