16
P
rec,ave
P
rec,max
ACS850 Type
kW kW
03A0-5, 03A6-5, 04A8-5, 06A0-5 3.5 4.4
08A0-5 4.7 5.9
010A-5 6.5 8.1
014A-5, 018A-5 10.8 13.5
025A-5, 030A-5, 035A-5 20.5 25.7
044A-5, 050A-5 29.2 36.5
061A-5, 078A-5, 094A-5 52.9 66.2
103A-5 61.0 77.1
144A-5 85.3 90.1
166A-5 98.2 103.6
202A-5 119.3 133.9
225A-5 133.3 154.8
260A-5 152.2 197.3
290A-5 171.7 215.4
430A-5 260.2 315.6
521A-5 315.3 351.3
602A-5 364.5 442.8
693A-5 419.5 511.2
720A-5 435.7 511.2
P
rec
values are defined at 540 V DC link voltage level, which corresponds to the
nominal 400 V AC supply voltage U
ac
. In case of other DC voltage levels (U
dc
), the P
rec
values in the table are multiplied by U
dc
/540 where
acdc
U.U
351 .
Chokes, braking choppers and charging circuits
Drive Frame Choke Braking
chopper
DC supply charging circuit
A, B - As standard Built-in
C, D DC As standard Built-in
ACS850
E0, E, G AC Optional External
Power requirements
In a common DC system, several drive modules are connected to the DC link. Each
drive and motor has its own specific load cycle profile. The sum of these load cycles
defines the system power profile in the DC link as shown in the figure below.