1  L1, L2, L3, PE (from top to down) 
2  U1, V1, W1 (from left to right) 
3  U2, V2, W2 (from left to right) 
4  DC+, DC- (from left to right) 
5  JCU connectors XPOW:2 and XRO:2 (from left to right) 
6  JCU connectors XD24:1 and XDI:A (from left to right) 
Drive module settings 
Note: The parameter settings mentioned below apply to ACS850 Standard Application 
Program. 
•  It is recommended to set parameter 99.05 MOTOR CTRL MODE to DTC and to 
adjust parameters 20.12 P MOTORING LIM and 20.13 P GENERATING LIM to limit 
the maximum power. The calculated braking power can also be used as the 
parameter value of 20.13 P GENERATING LIM. 
•  When brake chopper is used, set parameter 48.01 BC ENABLE. This activates the 
chopper when the DC voltage is high. Also the parameter 47.01 OVERVOLTAGE 
CONTROL must be disabled from all of the converters separately. 
•  All converters must be in the READY state before starting. See section READY 
signals for instructions on how to connect the READY signals. 
•  Switch on the possible DC contactors based on Table 1 after all of the DC links are 
charged and the converters are in the READY state, i.e. when the power is on and 
no faults appear. 
Common DC configurations