8 EN – USA quick installation guide
Install the drive on the wall
See figures A and B on page 81. For UL Type 12 drives: Install also the hood to the
drive as shown.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure D on page 86. Measure the insulation resistance between
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
please consult the manufacturer’s instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
Drive type Air flow Losses Fuse (one per phase)
(ft
3
/min) (W) Type
U
N
= 230 V
ACS880-01-046A-2 79 500 JJS-80
ACS880-01-061A-2 165 630 JJS-100
ACS880-01-075A-2 165 680 JJS-125
ACS880-01-087A-2 165 730 JJS-125
U
N
= 460V
ACS880-01-040A-5 79 667 JJS-60
ACS880-01-052A-5 165 907 JJS-80
ACS880-01-065A-5 165 1117 JJS-90
ACS880-01-077A-5 165 1120 JJS-110
U
N
= 525 V
ACS880-01-07A3-7 165 217 JJS-15
ACS880-01-09A8-7 165 284 JJS-20
ACS880-01-14A2-7 165 399 JJS-30
ACS880-01-018A-7 165 490 JJS-40
ACS880-01-022A-7 165 578 JJS-50
ACS880-01-026A-7 165 660 JJS-50
ACS880-01-035A-7 165 864 JJS-60
ACS880-01-042A-7 165 998 JJS-80
ACS880-01-049A-7 165 1120 JJS-80