Startup Assistant & Parameters 12-753AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
ENERGY
EFFICIENCY
(Continued)
COMPARISON POWER
(45.19)
Default: 0.0 kW
Range: 0.0 - 100000.0 kW
Actual power that the motor absorbs when connected direct-on-line
and operating the application. The value is used for reference when
energy savings are calculated.
Note: The accuracy of the energy savings calculation is directly
dependent on the accuracy of this value. If nothing is entered
here, then the nominal motor power is used by the calculation,
but that may inate the energy savings reported as many motors
do not absorb nameplate power.
ENERGY CALCULATIONS
RESET (45.21)
Default: 0 (Done)
Range: 0, 1
0 (Done) Reset not requested (normal operation), or reset complete.
1 (Reset)
Reset the savings counter parameters. The value reverts automatically to
Done.
Resets the savings counter parameters 45.01 - 45.09.
MONITORING/
SCALING
SETTINGS
Speed supervision settings; actual signal ltering; general scaling settings.
SPEED SCALING (46.01) Default: Max Speed (P 30.12)
Range: 0.10 to 30000.00 RPM
Denes the maximum speed value used to dene the acceleration ramp
rate and the initial speed value used to dene the deceleration ramp rate
(see parameter group 23 Speed reference ramp). The speed acceleration
and deceleration ramp times are therefore related to this value (not to
parameter 30.12 Maximum speed).
Also denes the 16-bit scaling of speed-related parameters. The value
of this parameter corresponds to 20000 in eldbus, master/follower etc.
communication.
TORQUE SCALING (46.03) Default: 100.0%
Range: 0.1 to 1000.0%
Denes the 16-bit scaling of torque parameters. The value of this
parameter (in percent of nominal motor torque) corresponds to 10000
in eldbus, master/follower etc. communication.
See also parameter 46.42 Torque decimals.
FILTER TIME MOTOR SPEED
(46.11)
Default: 10 ms
Range: 2 - 20000 ms
Denes a lter time for signals 01.01 Motor speed used, 01.02 Motor
speed estimated, 01.04 Encoder 1 speed ltered and 01.05 Encoder 2
speed ltered.
FILTER TIME OUTPUT
FREQUENCY (46.12)
Default: 500 ms
Range: 2 - 20000 ms
Denes a lter time for signal 01.06 Output frequency.
FILTER TIME MOTOR
TORQUE (46.13)
Default: 10 ms
Range: 2 - 20000 ms
Denes a lter time for signal 01.10 Motor torque %.