Startup Assistant & Parameters 12-833AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
EMBEDDED
FIELDBUS
(Continued)
ADDRESSING MODE (58.33) Default: 0 (Mode 0)
Range: 0 - 2
0 (Mode 0)
16-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 400000 + 100 × parameter group + parameter
index. For example, parameter 22.80 would be mapped to register
400000 + 2200 + 80 = 402280.
32-bit values (groups 1 - 99, indexes 1 - 99):
Register address = 420000 + 200 × parameter group + 2 × parameter
index. For example, parameter 22.80 would be mapped to register
420000 + 4400 + 160 = 424560.
1 ( Mode 1)
16-bit values (groups 1 - 255, indexes 1 - 255):
Register address = 400000 + 256 × parameter group + parameter
index. For example, parameter 22.80 would be mapped to register
400000 + 5632 + 80 = 405712.
2 ( Mode 2)
32-bit values (groups 1 - 127, indexes 1 - 255):
Register address = 400000 + 512 × parameter group + 2 × parameter
index. For example, parameter 22.80 would be mapped to register
400000 + 11264 + 160 = 411424.
Denes the mapping between parameters and holding registers in the
400101 - 465535 Modbus register range.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
WORD ORDER (58.34) Default: 1 (LO-HI)
Range: 0, 1
0 (HI-LO)
The rst register contains the high order word, the second contains
the low order word.
1 (LO-HI)
The rst register contains the low order word, the second contains the
high order word.
Selects in which order 16-bit registers of 32-bit parameters are
transferred.
For each register, the rst byte contains the high order byte and the
second byte contains the low order byte.
Changes to this parameter take effect after the control unit is rebooted
or the new settings validated by parameter 58.06 Communication
control.
EFB COMM SUPERVISION
FORCE (58.36)
Default: 0000b
Range: 0000b - 0111b
Activates eldbus communication monitoring separately for each
control location (see section Local control vs. external control).
The parameter is primarily intended for monitoring the communication
with EFB when it is connected to the application program and not
selected as a control source by drive parameters.
Bit Name Information
0
Ext 1
1 = Communication monitoring active
when Ext 1 is being used
1
Ext 2
1 = Communication monitoring active
when Ext 2 is being used
2
Local
1 = Communication monitoring active
when local control is being used
3-15
Reserved