ABB IB 6.2.15.7-1C
DRAWOUT - STANDARD WIRING:
The schematic shows the basic wiring
scheme for drawout breaker with standard
wiring. This wiring includes four “a” and four
“b” auxiliary contacts.
If the optional pin monitoring circuit is used,
only three “b” contacts will be available for
use.
The point-to-point diagram shows the
physical connections and wire numbers
used in the wiring harness.
FIXED-MOUNT/RETROFIT -
S
TANDARD WIRING:
The wiring scheme for the fixed-mount
breakers is exactly the same as that for the
drawout breakers. The only difference is
that the terminations ending in the
secondary disconnect plug on the drawout
breakers are provided as un-lugged wires
for connection to terminal strips.
APPENDICES
Standard Wiring Point-to-Point