Rated Current | 630 A to 6300 A |
---|---|
Number of Poles | 3 or 4 |
Frequency | 50/60 Hz |
Mounting | Fixed or withdrawable |
Standards | IEC 60947-2 |
Trip Unit | Electronic |
Insert moving parts into fixed parts for withdrawable versions.
Pull tie rod 'H' of X1-T7 upwards to bring tie rod 'J' of E1/E6 to 10 mm.
Pull tie rod 'P' of E1/E6 downwards to bring tie rod 'Q' of X1-T7 to 10 mm.
Perform opening/closing operations and check the 10 mm gap.
Close breaker 'A' and ensure breaker 'B' cannot be closed.
Reset breaker 'A' springs and verify it remains closed.
Close breaker 'B' and ensure breaker 'A' cannot be closed.
Reset breaker 'B' springs and verify it remains closed.
Repeat test thrice, check adjustments and tie-rod fastness.