EasyManua.ls Logo

ABB Circuit Shield 87B - APPLICATION; Voltage Settings - External Faults

ABB Circuit Shield 87B
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
High
-
Impedance
Differential
Relays
IB
7.6
.
1.7
-
7
Page
8
APPLICATION
The
Type
87
B
is
a
single
-
phase
relay
of
the
high
-
impedance
high
-
speed
type
.
It
is
used
in
well
known
differential
circuits
with
standard
current
transformers
.
Typically
,
three
type
87
B
relays
and
a
lockout
relay
are
required
in
standard
configurations
for
bus
differential
protection
against
phase
-
to
-
phase
and
phase
-
to
-
ground
faults
.
A
properly
set
relay
will
discriminate
between
external
(
through
feed
)
and
internal
system
faults
.
The
relay
is
a
voltage
actuated
device
but
its
pick
-
up
sensitivity
is
proportional
to
current
magnitudes
during
internal
faults
.
The
voltage
across
the
relay
input
is
practically
zero
in
symmetrical
circuits
during
normal
operation
,
hence
the
continuous
input
rating
is
of
less
importance
.
Moderate
voltage
may
appear
in
the
secondary
circuits
due
to
unequal
performance
or
saturation
of
some
CT
'
s
.
However
,
these
voltages
will
result
in
smaller
differential
currents
(
in
percent
)
than
in
schemes
with
low
impedance
differential
relays
.
Thus
,
high
differential
impedance
(
usually
several
orders
of
magnitude
higher
than
the
shunt
impedance
of
saturated
CT
'
s
)
leaves
current
transformers
force
-
coupled
through
their
secondaries
and
allows
better
discrimination
between
faults
.
Internal
faults
lead
to
summation
of
all
infeed
secondary
currents
in
the
relay
with
some
shunting
effect
of
idle
CT
secondaries
.
Relay
voltage
and
current
rise
rapidly
during
heavy
internal
faults
.
The
signal
,
while
being
voltage
-
limited
by
varistors
,
causes
the
relays
to
operate
and
self
-
protect
the
input
of
87
B
relay
until
circuit
breakers
trip
.
All
differential
relays
of
high
-
impedance
type
have
limited
input
current
or
energy
ratings
.
The
described
protection
can
be
conveniently
expanded
to
more
CT
'
s
if
breakers
are
added
to
the
existing
scheme
.
The
standard
Type
87
B
relay
does
not
contain
restraining
circuits
.
Applications
which
involve
either
lightning
arresters
(
directly
connected
to
the
bus
)
or
non
-
relayed
capacitors
with
grounded
mid
-
points
or
other
equipment
subject
to
high
magnetizing
inrush
or
non
-
canceled
infeed
should
be
referred
to
the
factory
.
Application
of
the
Type
87
B
relay
and
calculation
of
proper
settings
require
consideration
of
the
above
described
properties
of
the
scheme
.
In
general
and
to
provide
optimum
performance
,
attention
is
recommended
to
:
proper
selection
of
current
transformers
and
wiring
,
voltage
settings
above
voltages
and
transients
expected
under
external
fault
or
inrush
conditions
,
sensitivity
to
internal
faults
,
and
relay
withstand
at
maximum
fault
magnitudes
.
For
example
,
the
following
selection
procedures
can
be
adapted
for
a
given
bus
differential
protection
scheme
:
Voltage
Settings
-
External
Faults
The
relay
should
be
set
above
maximum
secondary
circuit
voltage
which
will
appear
during
external
faults
.
Assume
that
the
CT
of
a
faulted
feeder
or
load
breaker
is
completely
saturated
and
one
or
more
source
CT
'
s
are
forcing
current
through
its
secondary
winding
.
1
.
Identify
ratio
and
location
of
CT
'
s
.
Obtain
or
calculate
DC
resistance
of
the
secondary
winding
of
the
CT
and
two
-
way
lead
length
from
the
junction
point
to
the
farthest
CT
.
Correct
resistance
values
to
the
highest
ambient
or
operating
temperature
.
2
.
Obtain
interrupting
rating
of
the
largest
circuit
breaker
(
symm
.
A
RMS
)
referred
to
secondary
side
of
CT
'
s
.
3
.
Product
of
this
current
and
resistance
sum
obtained
above
is
symmetrical
AC
RMS
voltage
.
4
.
To
obtain
minimum
relay
setting
,
multiply
this
value
by
a
factor
(
e
.
g
.
2.5
)
which
will
account
for
safe
margins
,
DC
offset
,
resistance
tolerances
and
current
transfer
between
CT
s
.
5
.
The
voltage
thus
calculated
represents
the
minimum
safe
setting
of
the
relay
.
If
the
value
is
between
set
points
,
use
the
next
higher
pickup
setting
.
Still
higher
settings
will
provide
additional
safety
margins
with
some
increase
in
detectable
internal
fault
magnitude
.
In
most
cases
,
the
voltage
pickup
of
the
87
B
relay
can
be
set
above
the
saturation
voltage
rating
(
knee
point
)
of
CT
s
.
Courtesy of NationalSwitchgear.com

Related product manuals