EasyManuals Logo

ABB Circuit Shield 87B User Manual

ABB Circuit Shield 87B
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
High
-
Impedance
Differential
Relays
IB
7.6
.
1.7
-
7
Page
9
These
conservative
calculations
can
be
refined
to
produce
lower
settings
if
the
following
or
other
practical
conditions
are
considered
:
Maximum
fault
current
is
usually
lower
than
interrupting
ratings
.
Faulted
circuit
CT
'
s
of
standard
design
never
saturate
completely
.
Source
CT
'
s
may
enter
saturation
region
.
Phase
-
to
-
ground
external
fault
currents
in
resistance
grounded
systems
are
relatively
low
,
hence
3
-
phase
fault
currents
and
one
-
way
lead
resistance
become
the
controlling
factors
.
Junction
points
of
leads
may
not
be
equidistant
but
closer
to
CT
'
s
of
feeders
which
are
subject
to
external
faults
.
Withstand
-
Internal
Faults
The
thermal
withstand
of
the
relay
is
controlled
by
internal
dissipation
limits
.
Energy
depends
on
the
speed
of
the
differential
and
lockout
relay
operation
,
maximum
available
fault
current
,
and
CT
saturation
characteristics
.
In
general
,
the
wattsecond
rating
of
high
impedance
relays
of
any
type
should
be
checked
against
expected
energy
.
For
convenience
,
one
could
use
a
simplified
method
as
reflected
in
Table
2
that
is
based
on
limits
of
CT
saturation
voltages
with
respect
to
relay
currents
and
a
conservative
total
operating
time
of
40
milliseconds
(
from
inception
of
the
fault
to
closing
instant
of
the
lockout
relay
contacts
)
.
Table
2
Typical
Input
Current
and
Energy
Limits
Current
Transformers
Max
Current
Transformers
Max
system
fault
current
(
Symm
RMS
)
Max
.
relay
Current
(
Symm
RMS
)
Max
.
system
fault
current
(
Symm
RMS
)
Max
relay
Current
(
Symm
RMS
)
Current
Transformers
Max
system
fault
current
Symm
RMS
)
relay
Current
(
Symm
RMS
)
Minimum
Ratio
Max
Max
.
Satur
.
Voltage
Minimum
Ratio
Minimum
Ratio
Max
Satur
.
Voltage
Satur
.
.
Voltage
170
A
240
V
1500
:
5
1200
:
5
800
:
5
50
KA
37.5
KA
25
KA
100
A
2500
:
5
2000
:
5
1500
:
5
50
KA
37.5
KA
25
KA
350
V
300
A
170
V
1000
:
5
800
:
5
500
:
5
50
KA
37.5
KA
25
KA
150
A
260
V
50
KA
37.5
KA
25
KA
90
A
2000
:
5
1500
:
5
1000
:
5
360
V
3000
:
5
2500
:
5
1500
:
5
50
KA
37.5
KA
25
KA
250
A
200
V
1000
:
5
800
:
5
500
:
5
135
A
50
KA
37.5
KA
25
KA
280
V
2000
:
5
1500
:
5
1000
:
5
50
KA
37
.
5
KA
25
KA
75
A
4000
:
5
2500
:
5
2000
:
5
400
V
50
KA
37.5
KA
25
KA
220
A
210
V
1200
:
5
1000
:
5
600
:
5
50
KA
37.5
KA
25
KA
125
A
290
V
2000
:
5
1500
:
5
1000
:
5
50
KA
37.5
KA
25
KA
62
A
440
V
4000
:
5
3000
:
5
2000
:
5
50
KA
37.5
KA
25
KA
200
A
220
V
1500
:
5
1000
:
5
800
:
5
50
KA
37.5
KA
25
KA
310
V
110
A
2500
:
5
2000
:
5
1200
:
5
50
KA
37.5
KA
25
KA
40
A
600
V
(
*
)
50
KA
37.5
KA
25
KA
(
*
)
4000
:
5
(
*
)
CT
'
s
in
this
range
are
not
widely
available
due
to
limited
window
area
.
Consult
factory
.
If
the
maximum
fault
current
(
in
symmetrical
RMS
amperes
)
and
the
ratio
are
known
,
the
selected
saturation
voltage
of
any
CT
should
not
be
higher
than
indicated
on
the
corresponding
line
.
Conversely
,
the
CT
ratio
should
not
be
lower
than
one
shown
for
corresponding
values
of
the
system
fault
current
and
CT
saturation
voltage
.
Intermediate
values
can
be
obtained
by
interpolation
.
Alternatively
,
the
energy
can
be
accurately
calculated
from
the
instantaneous
product
of
secondary
'
current
and
voltage
pulses
.
One
should
bear
in
mind
,
however
,
that
the
total
circuit
is
not
linear
during
faults
.
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Circuit Shield 87B and is the answer not in the manual?

ABB Circuit Shield 87B Specifications

General IconGeneral
BrandABB
ModelCircuit Shield 87B
CategoryRelays
LanguageEnglish

Related product manuals