CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E 133
Process values Counter
Current output
Priority
Error text
Qm [%, unit]
Qv [%, unit]
Density [g/cm
3
]
Temperature [°C]
Concentration [%]
Net mass flow
Standard density g/cm
3
]
Standard volume [20 °C]
All counters
59 Density too low.Empty pipe, gas 0 0 0 0
58 Density to 1g/cm³ 2) 1 2) 2) 2) 2)
57 Sensor temperature out max range
1) 1) 1) 20 1) 1) 1) 1)
54 Sensor amplitude out of ranges – – – – – – – –
52 Curr.Out 31/32 is saturated.
– – – – – – – –
CO 31 / 32, U
CO
only:
HOLD,
, (configurable)
51 Curr.Out V1/V2, V3/V4 saturated
– – – – – – – –
CO V1 / V2, CO V2 / V3:
HOLD,
, (configurable)
49 Option Card 1 com error.
– – – – – – – –
CO V1 / V2:
48 Option Card 2 com error.
– – – – – – – –
CO V2 / V3:
47 Pulse output is cut off. – – – – – – – –
46 Mass flowrate exceeds limits. – – – – – – – –
44 Volume flowrate exceeds limits. – – – – – – – –
43 Density exceeds min/max limits. – – – – – – –
42 Medium temperat exceeds limits. – – – – – – – –
41 Concentration inunit exceeds – – – – – – – –
40 Concentration in percent exceeds – – – – – – – –
38 Sensor memory defective. – – – – – – – –
37 NV chips defect on Motherboard. – – – – – – – –
32 Curr.Out 31/32 not calibrated. – – – – – – – –
31 Curr.Out V1/V2 not calibrated. – – – – – – – –
30 Curr.Out V3/V4 not calibrated. – – – – – – – –
28 Display value is <1600h at Qmax. – – – – – – – –
26 Maintenance interval is reached – – – – – – – –
24 Device not calibrated. – – – – – – – –
20 Communicat. card not responding – – – – – – – –