35
M1M 30 POWER METER USER MANUAL
Options Description
- None
WH
Active energyKWH
MWH
VARH
Reactive energyKVARH
MVARH
VAH
Apparent energyKVAH
MVAH
Pulse settings (PULS)
PULS includes selection of energy variables of panel LED indicator, energy pulse output ratio, and 
selection of energy variables of the DO set as PULSE. 
   CONF   IO   PULSE
The optional output energy variables of LED indicator and DO include:
Electricity Variable  Description
PEN Active energy
QEN Reactive energy
OFF Off 
The setting range of pulse output ratio is: 0.001 ... 9999. The formula guiding this parameter setting is:
1 pulse = X Wh (varh/VAh)
 X is the set number.