EasyManua.ls Logo

ABB PSTX Series - Page 12

ABB PSTX Series
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Quick start | Installation and commissioning manual | 1SFC132081M0201
This chapter is a short guide on how to connect,
configure and start the Softstarter in an easy way.
This product was carefully manufactured and tested, but
damage can occur during transportation. Therefore, obey
these instructions:
WARNING
Dangerous voltage: Can cause death or serious
injury. Always set the power switch to off and lock
out all power to this device before you start to
work on the equipment.
WARNING!
Installation of electrical connections must be done by
authorized personnel. Obey all laws and regulations.
WARNING!
Before you connect the Softstarters PSTX30...
PSTX170 to the operation voltage for the first time,
apply control supply voltage to open the bypass
relays. (see 2.1 Connection). This is necessary to
avoid an accidental start of the equipment while it is
connected to operation voltage.
INFORMATION
ABB personnel must obey the instructions in
ABB CISE 15.4.
2.1 Connection
1. To install the Softstarter
see chapter 4 Installation.
INFORMATION
You can connect PSTX Softstarters In Line
1
and
Inside Delta
2
, see Figure 2.1.
2. Connect the main circuit: terminals 1L1 - 3L2 -
5L3 to the line side
1
, and terminals 2T1 - 4T2
- 6T3 to the motor side
2
, see Figure 2.2.. Use
wire connection for PSTX30...105, see Figure 2.2
and terminal connection for PSTX142...570, see
Figure 2.3.
3. Connect the line side to terminals 1L1, 3L2, 5L3.
see
1
and Figure 2.2. Connect the motor to
terminals 2T1, 4T2, 6T3 on the motor side, see
2
Figure 2.2 and Figure 2.3.
INFORMATION
Use only wires of the same dimension when you
connect 2 wires to each terminal. (Possible for
PSTX30...105 only).
4. Connect the control supply voltage (100-250V
50/60Hz) to terminal 1 and 2.
5. Connect the functional ground (terminal 22), to a
ground point close to the Softstarter,
see Figure 2.4.
1 2
Figure 2.1
In Line (1) and Inside Delta (2) connection
PSTX
PSTX
1SFC132081M0201
1
2
Figure 2.2
Terminal connection clamps
1SFC132081M0201
Line side
1L1
3L2
5L3
6T3
4T2
2T1
Motor side
Figure 2.3
Terminal connection bars
Line side
2T1
4T2
6T3
5L3
3L2
1L2
Motor side
1SFC132081M0201
2
1
2