1MRK 505 350-UEN Section 2
Signals
Technical Manual 11
Distributed busbar protection REB500
Table 7 BU input signals for BFP, EFP, OCDT, and PDF
Signal Description
12605_Bypass Check Zone
The check zone criterion for the release of the bus bar protection
is bypassed.
13205_Block BFP
Blocks
operation of BFP for the corresponding bay unit. When the
blocking signal is cancelled, the timers start again at t
=
0.
13210_BP Block BFP
Blocks operation of BFP of the corresponding feeder. When the
blocking signal is cancelled and providing a starting signal is
present and current is flowing, the timers start again at t = 0.
13605_Trip
r
edirection
_1
The circuit
-
breaker sets this input when it cannot open, e.g.
because the air pressure is too low or there is a leak in the case
of GIS (Alarm Stage 3 - Circuit-breaker blocked). A tripping signal
is then transferred to the adjacent breakers (busbar trip) and
possibly the remote station.
1360
6
_Trip
redirection_2
Reserved for special applications
.
If this signal is set then the trip redirection is active in the same
way as it is for the 13605_Trip redirection _1.
This signal must not be used for pressure low input from circuit-
breaker.
13610_BP Trip transfer
Reserved for special applications
.
This Bay Protection (BP) signal allows triggering the trip
redirection functionality if the signal "13605_Trip redirection _1" or
"13606_Trip redirection_2" is active.
This signal is directly activated by BP and does not therefore
appear as a binary input signal.
13705_External Start BFP
A signal applied to
this input starts the breaker failure protection
timer (independently of the overcurrent measurement).
13710...13735_Start BFP Lp_x
Phase
-
selective (p
=
1 to 3) starting of the breaker failure
protection with two inputs per phase (x = 1 to 2). The breaker
failure timer is started by this input signal providing the current in
the respective phase is above pick-up.
13740...13765_Start BFP
L1L2L3_x
Three
-
phase starting of BFP by six inputs (x
=
1 to 6). The BFP
timer is started by a signal at one of these inputs providing the
current in at least one phase is high enough.
13761_BP Start BFP L1L2L3_5
Functionally identical to signal "13760_Start BFP L1L2L3_5" but
directly activated by the bay protection unit and not appearing as
binary input signal.
13770...1
3780_BP Start BFP Lp
BFP with phase
-
selective starting (p
=
1, 2 or 3). The BFP timer
starts when this signal is activated by the bay protection function
and the BFP measures a current in the corresponding phase.
13785_BP
Start BFP
L1L2L3
BFP with
three
-
phase starting. The BFP timer starts when this
signal is activated and the BFP measures a current in any phase.
13790_BP External start BFP
BFP with three
-
phase starting. The BFP timer starts when this
signal is activated regardless of the current
measurement.
13795...13796_Start BFP L0_x
L0
-
starting of BFP with two inputs (x
=
1 or 2). The BFP timer is
started by this input signal providing the current in the neutral
system is above pick
-
up.
13797_BP Start BFP L0
Breaker failure protection with
L0
-
starting. The breaker failure
protection timer starts when this signal is activated by the bay
protection function and the BFP measures a current in the neutral
system.
13805
_
Start
BFP
Q0
no
I_1
13810_Start BFP Q0 no I_2
The BFP timer starts when th
is signal is activated
and the
Breaker (11530_Breaker Position) is closed and valid
(independently of the overcurrent measurement).