Section 2 1MRK 505 350-UEN
Signals
16 Technical Manual
Distributed busbar protection REB500
Signal Description
31805_External release BB
zone
Enables the tripping signal for a section of busbar (AND gate with
tripping and enabling inputs). A maximum of 12 bus zones resp.
external release signals can be configured in one BIO unit. The entire
protection zone surrounding the busbar section is enabled (transfer
tripping). Sections connected by isolators are also enabled (transfer
tripping). The input can be used in special cases, for example, to
interlock the tripping signal by an undervoltage relay. This will
generally delay tripping.
With this signal of the bus bar protection the inter
external trip of the BB block is blocked. A maximum of 12 bus zones
resp. blocking signals can be configured in one BIO unit. A complete
bus zone in which the BB block is located would be blocked (inter-
tripping). If the bus block is associated with an isolator then it is also
blocked (inter-tripping).
The input operates with a time delay of up to 300 ms.
Tripping commands and signals can be configured to latc
they are, they are reset by a signal applied to this input. The same
signal also resets the LED’s (alarm and tripping). The reset signal
applies to the entire system.
service_1
Inputs for monitoring any fans, external supp
41805_Alarm is set in the central unit when any of these signals
changes from logical 1 to 0.
service_2
With a properly configured event configuration, the input signal can
be transmitted IEC103 and displayed on the control system.
Table 17 CU input signals for protection functionality
Signal Description
Blocks BBP throughout the system.
Check Zone
Bypasses the check zone criterion for the
Blocks BFP throughout the system. When cancelled, the timers start again at
t = 0 if the current is higher than setting.
Blocks EFP throughout the system. When cancelled, the timers start again at
t = 0 if the circuit-breaker is open and the current higher than setting.
OCDT
Blocks OCDT throughout the system. When cancelled, the timers start again at
t = 0.
Start DR
The disturbance recorders in all the bay units are started by this
configured. The signal “General start disturbance recorder” must also be
configured in the bay units. The disturbance recorder in the central unit is not
Blocks PDF throughout the system. The timers restar
reset.
Blocks bay protection output signals throughout the system. Internal processing
of the functions continues and therefore measurements and signals continue to
be displayed on the local HMI.
Binary input signals cannot be used to trigger a disturbance record
in the central unit.