Section 6 1MRK 505 350-UEN
Additional functions
58 Technical Manual
Distributed busbar protection REB500
Releasing “BBP_L1L2L3”, “BBP_L0”, “External TRIP BB Zone (CU)” and
“External TRIP BB Zone (BU)” always involves enabling intertripping of the
respective protection zone.
Releasing “OCDTand “PDF” always involves enabling the respective
function and only applies if the feeder is connected to the respective protection
zone. This is determined by the intertripping logic.
Releasing “BFP” and “EFP” in columns 1 to 4 involves enabling intertripping
of these functions (e.g. BFP trip after t2).
Figure 26 Release criteria
Table 37 Release criteria
Release criterion Description
U only
Can only be select
ed if the voltage release function has been configured.
External release input
only
Can only be selected if input “31805_External release BB
-
zone” has been
configured.
U AND external release
input
“AND” logic of the voltage release criterion and the
input “31805_External
release BB-zone”. This can only be selected if the voltage release criterion
and the input “31805_External release BB-zone” have been configured.
U OR external release
input
“OR” logic of the voltage release criterion and the input “
31805_External
release BB-zone”. This can only be selected if the voltage release criterion
and the input “31805_External release BB-zone” have been configured.
Release corresponding
BU function
Can only be selected if a corresponding criterion in the oth
er 4 columns has
been configured.