3.2.3 Input/output signal interface
Table 6: Binary input interface
Hardware module
instance
Hardware channel Usage
COM BI1 Generator circuit breaker close
COM BI2 Generator circuit breaker open
COM BI3 Generator circuit breaker truck close
COM BI4 Generator circuit breaker truck open
COM BI5 Earthing switch close
COM BI6 Earthing switch open
COM BI7 NGR switch close
COM BI8 NGR switch open
COM BI9 Operate signal from AVR
COM BI10 Operate signal from turbine
COM BI11 Lockout reset
COM BI12 Generator circuit breaker gas pressure (lockout)
COM BI13 Generator circuit breaker spring charged
COM BI14 Voltage transformer MCB open
The IED outputs are categorized as power outputs (POx) and signal outputs (SOx).
The power outputs can be used for starting and stopping the motor. The signal outputs
are not heavy-duty outputs. They are used for alarm or signalling purposes.
Table 7: Binary output interface
Hardware module
instance
Hardware channel Usage
PSM PO1 Master Trip 1 (generator circuit breaker open)
PSM PO2 Generator circuit breaker close enable signal
PSM PO3 Master Trip 2 (generator circuit breaker open)
PSM PO4 Operate from directional over power protection
PSM PO5 Operate from differential protection
PSM PO6 Operate from frequency protection
PSM SO1 Common generator circuit breaker operate signal
PSM SO2 Common generator circuit breaker start signal
PSM SO3 Generator circuit breaker trip circuit and monitoring alarm
The IED measures the analog signals needed for protection and measuring functions
via galvanically-isolated matching transformers. The matching transformer input
channels 1…7 are intended for current measuring, and the channels 8...10 for voltage
measuring.