EasyManua.ls Logo

ABB REG630 - Binary Recording and LED Configuration

ABB REG630
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.2.9 Binary recording and LED configuration
All the start and operate outputs from the respective protection functions, various
alarms from supervision functions, and important signals from control and protective
functions are connected to a binary recorder. In case of a fault, the binary recorder is
triggered and all the signals connected to the recorder are recorded.
Table 10: Signals connected to binary recorder
Channel ID Description
Channel 1 Operate of differential protection high stage
Channel 2 Operate of differential protection low stage
Channel 3 Differential protection internally blocked
Channel 4 Start of overcurrent low stage
Channel 5 Operate of overcurrent low stage
Channel 6 Start of overcurrent high stage
Channel 7 Operate of overcurrent high stage
Channel 8 Start of voltage controlled overcurrent stage 1
Channel 9 Operate of voltage controlled overcurrent stage 1
Channel 10 Start of voltage controlled overcurrent stage 2
Channel 11 Operate of voltage controlled overcurrent stage 2
Channel 12 Start of negative sequence overcurrent stage 1
Channel 13 Operate of negative sequence overcurrent stage 1
Channel 14 Start of negative sequence overcurrent stage 2
Channel 15 Operate of negative sequence overcurrent stage 2
Channel 16 Thermal overload prior alarm
Channel 17 Operate thermal overload
Channel 18 Start of directional earth fault low stage
Channel 19 Operate of directional earth fault low stage
Channel 20 Start of directional earth fault high stage
Channel 21 Operate of directional earth fault high stage
Channel 22 Start of phase overvoltage protection stage 1
Channel 23 Operate of phase overvoltage protection stage 1
Channel 24 Start of phase overvoltage protection stage 2
Channel 25 Operate of phase overvoltage protection stage 2
Channel 26 Start of phase undervoltage protection stage 1
Channel 27 Operate of phase undervoltage protection stage 1
Channel 28 Start of phase undervoltage protection stage 2
Channel 29 Operate of phase undervoltage protection stage 2
Channel 30 Start of residual overvoltage protection stage 1
Channel 31 Operate of residual overvoltage protection stage 1
Channel 32 Start of residual overvoltage protection stage 2
Table continues on next page
1MRS757582 C Section 3
REG630 variants
REG630 47