EasyManua.ls Logo

ABB Relion 670 series - Page 110

ABB Relion 670 series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M14964-1 v13
Table 80. Underfrequency protection SAPTOF
Function Range or Value Accuracy
Operate value, start function,
at symmetrical three phase
voltage,
StartFrequency
1)
(35.00 - 90.00) Hz ±2.0 mHz
Reset hysteresis
1)
10.0 mHz fixed ±2.0 mHz
Operate time
1)
fr = 50 Hz
Start time measurement with
sudden frequency change
Min. = 175 ms -
Max. = 195 ms
Start time measurement with
frequency ramp
Min. = 70 ms
Max. = 90 ms
fr = 60 Hz
Start time measurement with
sudden frequency change
Min. = 150 ms -
Max. = 165 ms
Start time measurement with
frequency ramp
Min. = 60 ms
Max. = 75 ms
Disengaging time
1)
fr = 50 Hz
Start time measurement with
sudden frequency change
Min. = 20 ms -
Max. = 30 ms
Start time measurement with
frequency ramp
Min. = 75 ms
Max. = 100 ms
fr = 60 Hz
Start time measurement with
sudden frequency change
Min. = 20 ms -
Max. = 30 ms
Start time measurement with
frequency ramp
Min. = 65 ms
Max. = 90 ms
Operate time delay,
tDelay
1)
fr = 50 Hz
(0.000-60.000)s
±0.2% or ±200 ms
whichever is greater
fr = 60 Hz ±0.2% or ±175 ms
whichever is greater
Note: The stated accuracy is valid for the voltage range 50 V – 250 V secondary.
1) The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 6.7).
M14976-1 v10
Table 81. Rate-of-change of frequency protection SAPFRC
Function Range or value Accuracy
Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s
Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz
Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is greater
Definite time delay for frequency gradient
trip
(0.000-60.000) s ±0.2% or ±120 ms whichever is greater
Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is greater
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
110 Hitachi Power Grids
© Copyright 2017 Hitachi Power Grids. All rights reserved

Other manuals for ABB Relion 670 series