Logic
M12380-1 v15
Table 107. Tripping logic common 3-phase output SMPPTRC
Function Range or value Accuracy
Trip action,
Program
3 phase, 1ph/2ph,
1ph/2ph/3ph
-
Minimum trip pulse
length ,
tTripMin
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay,
tWaitForPHS
(0.020-0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay
,
tEvolvingFault
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater
GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1
Table 108. Number of SMAGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
SMAGAPC 12 - -
Table 109. Number of STARTCOMB instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
STARTCOMB 32 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3
Table 110. Number of TMAGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2
Table 111. Number of ALMCALH instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2
Table 112. Number of WRNCALH instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
WRNCALH - - 5
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
Hitachi Power Grids 125
© Copyright 2017 Hitachi Power Grids. All rights reserved