Table 200. RI and RD type inverse time characteristics for Line differential protection
Function Range or value Accuracy
RI type inverse characteristic
EQUATION1137-SMALL V1 EN-US
I = I
measured
/I
set
0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0%
or ±40 ms whichever is
greater
RD type logarithmic inverse
characteristic
5.8 1.35= - ×
æ ö
ç ÷
è ø
t
I
In
k
EQUATION1138-SMALL V1 EN-US
I = I
measured
/I
set
GUID-771E5218-2913-4BB0-B1EE-2CA1E912AEAA v1
Table 201. ANSI Inverse time characteristics for Line Differential Protection
Function Range or value Accuracy
Operating characteristic:
EQUATION1249-SMALL V3 EN-US
Reset characteristic:
EQUATION1250-SMALL V1 EN-US
I = I
measured
/I
set
k = (0.05-2.00) in steps of 0.01 ANSI/IEEE C37.112 , ±
5.0% or ± 40 ms
whichever is greater
ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1
ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6