Table 252. Station communication, remote end serial communication and time synchronization selection
Station communication, remote end
serial communication and time
synchronization
Ordering no Selection Notes and rules
Slot position (front view/rear
view)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
1)
Available slots in 1/2, 3/4 and 1/1
case with 1 TRM
2)
Available slots in 3/4 and 1/1 case
with 2 TRM
No communication board included X X X X X X X X X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K
3)
Ethernet SFP, RJ45 connector 1MRK005500-BA P P P P P P
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC
60870-5-103 plastic interface
1MRK001608-AB L
Serial SPA/LON/DNP/IEC
60870-5-103 plastic/glass
interface
1MRK001608-BB M
Serial SPA/LON/DNP/IEC
60870-5-103 glass interface
1MRK001608-CB N
Galvanic RS485 communication
module
1MRK002309-AA G G G
4)
Optical short range LDCM, 820 nm 1MRK002122-AB A A A A A A
5)
Optical medium range LDCM, 1310
nm
1MRK002311-AA B B B B B B
Optical long range LDCM, 1550 nm 1MRK002311-BA C C C C C C
Galvanic X21 line data
communication module
1MRK002307-AA E E E E
Line data communication, default
64kbps mode
X
Allow line data communication in
2Mbps mode
1MRK007002-AA Y
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization
module, with PPS
1MRK002305-AA F F F F
Selected
1) The maximum number and type of LDCM modules supported depend on the total amount of I/O and communication modules in the IED.
2) Max 2 LDCM in 1/2 case
3) Ethernet SFP is basic in P30:1. P30:6:1 and P30:6:2 require the Optical Ethernet module in P30:6.
4) RS485 not allowed in slot X312
5) Max 4 LDCMs can be ordered. Always place LDCM modules on the same board to support redundant communication: in P30:5 and P30:6, P31:2 and P31:3 or P32:2 and P32:3.
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
170 Hitachi Power Grids
© Copyright 2017 Hitachi Power Grids. All rights reserved

Other manuals for ABB Relion 670 series