Reservation function QCRSV
M13506-3 v5
The purpose of the reservation (QCRSV) function is
primarily to transfer interlocking information between
IEDs in a safe way and to prevent double operation in a
bay, switchyard part, or complete substation.
Reservation input RESIN
M16501-3 v6
The Reservation input (RESIN) function receives the
reservation information from other bays. The number of
instances is the same as the number of involved bays
(up to 60 instances are available).
Bay control QCBAY
M13447-3 v8
The Bay control (QCBAY) function is used together with
Local remote and local remote control functions to
handle the selection of the operator place per bay.
QCBAY also provides blocking functions that can be
distributed to different apparatuses within the bay.
Proxy for signals from switching device via GOOSE
XLNPROXY
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
The proxy for signals from switching device via GOOSE
(XLNPROXY) gives an internal representation of the
position status and control response for a switch
modelled in a breaker IED. This representation is
identical to that of an SXCBR or SXSWI function.
GOOSE function block to receive a switching device
GOOSEXLNRCV
GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1
The GOOSE XLN Receive component is used to collect
information from another device’s XCBR/XSWI logical
node sent over process bus via GOOSE. The GOOSE XLN
Receive component includes 12 different outputs (and
their respective channel valid bits) with defined names
to ease the 61850 mapping of the GOOSE signals in the
configuration process.
Local remote LOCREM/Local remote control
LOCREMCTRL
M17086-3 v11
The signals from the local HMI or from an external local/
remote switch are connected via the function blocks
local remote (LOCREM) and local remote control
(LOCREMCTRL) to the Bay control (QCBAY) function
block. The parameter
ControlMode
in function block
LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware
switch connected via binary inputs.
Logic rotating switch for function selection and
LHMI presentation SLGAPC
SEMOD114908-4 v11
The logic rotating switch for function selection and
LHMI presentation (SLGAPC) (or the selector switch
function block) is used to get an enhanced selector
switch functionality compared to the one provided by a
hardware selector switch. Hardware selector switches
are used extensively by utilities, in order to have
different functions operating on pre-set values.
Hardware switches are however sources for
maintenance issues, lower system reliability and an
extended purchase portfolio. The selector switch
function eliminates all these problems.
Selector mini switch VSGAPC
SEMOD158756-5 v10
The Selector mini switch (VSGAPC) function block is a
multipurpose function used for a variety of applications,
as a general purpose switch.
VSGAPC can be controlled from the menu, from a symbol
on the single line diagram (SLD) on the local HMI or from
Binary inputs.
Generic communication function for Double Point
indication DPGAPC
SEMOD55850-5 v7
Generic communication function for Double Point
indication (DPGAPC) function block is used to send
double point position indications to other systems,
equipment or functions in the substation through IEC
61850-8-1 or other communication protocols. It is
especially intended to be used in the interlocking
station-wide logics.
Single point generic control 8 signals SPC8GAPC
SEMOD176462-4 v11
The Single point generic control 8 signals (SPC8GAPC)
function block is a collection of 8 single point
commands that can be used for direct commands for
example reset of LEDs or putting IED in "ChangeLock"
state from remote. In this way, simple commands can be
sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary
inputs and SPGAPC function blocks. The commands can
be pulsed or steady with a settable pulse time.
Automation bits, command function for DNP3.0
AUTOBITS
SEMOD158591-5 v9
Automation bits function for DNP3 (AUTOBITS) is used
within PCM600 to get into the configuration of the
commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions
GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for
LON).
Single command, 16 inputs
M12446-6 v6
The IEDs can receive commands either from a
substation automation system or from the local HMI.
The command function block has outputs that can be
used, for example, to control high voltage apparatuses
or for other user defined functionality.
14. Scheme communication
Scheme communication logic with delta based
blocking scheme signal transmit ZCPSCH
M13860-3 v11
To achieve instantaneous fault clearance for all line
faults, scheme communication logic is provided. All
Line differential protection RED670
1MRK 505 379-BEN N
Hitachi Power Grids 45
© Copyright 2017 Hitachi Power Grids. All rights reserved