EasyManua.ls Logo

ABB Relion 670 series - Accessing the Maintenance Menu; Recovering Passwords and IED Defaults

ABB Relion 670 series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v8
Table 48. High speed distance protection ZMFPDIS, ZMFCPDIS
Function Range or value Accuracy
Number of zones 5 selectable
directions, 2 fixed
directions
-
Minimum operate current, Ph-
Ph and Ph-E
(5-6000)% of IBase ±1.0% of I
r
Positive sequence reactance
reach, Ph-E and Ph-Ph loop
(0.01 - 3000.00)
ohm/p
Pseudo continuous ramp:
±2.0% of set value
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: At 0 degrees and 85 degrees
IEC 60255-121 points A,B,C,D,E
Ramp of shots:
±2.0% of set value
Conditions:
IEC 60255-121 point B
Positive sequence resistance
reach, Ph-E and Ph-Ph loop
(0.00 - 1000.00)
ohm/p
Zero sequence reactance reach (0.01 - 9000.00)
ohm/p
Zero sequence resistive reach (0.00 - 3000.00)
ohm/p
Fault resistance reach, Ph-E
and Ph-Ph
(0.01 -9000.00)
ohm/l
Dynamic overreach < 5% at 85 degrees
measured with CVTs
and 0.5 < SIR < 30,
IEC 60255-121
-
Reset ratio 105% typically -
Directional blinders Forward: -15 – 120
degrees
Reverse: 165 – -60
degrees
Pseudo continuous ramp:
±2.0 degrees, IEC 60255-121
Resistance determining the
load impedance area - forward
(0.01 - 5000.00)
ohm/p
Pseudo continuous ramp:
±2.0% of set value
Conditions:
Tested at ArgLd = 30 degrees
Ramp of shots:
±5.0% of set value
Conditions:
Tested at ArgLd = 30 degrees
Angle determining the load
impedance area
5 - 70 degrees Pseudo continuous ramp:
±2.0 degrees
Conditions:
Tested at RLdFw = 20 ohm/p
Definite time delay to trip, Ph-E
and Ph-Ph operation
(0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
Operate time 16 ms typically, IEC
60255-121
-
Reset time at 0.1 to 2 x Zreach Min. = 20 ms
Max. = 35 ms
-
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
Hitachi Power Grids 89
© Copyright 2017 Hitachi Power Grids. All rights reserved

Other manuals for ABB Relion 670 series