EasyManua.ls Logo

ABB Relion 670 series - Page 93

ABB Relion 670 series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wide area measurement system
GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5
Table 56. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT
Influencing quantity Range Accuracy
Signal frequency ± 0.1 x f
r
≤ 1.0% TVE
Signal magnitude:
Voltage phasor
Current phasor
(0.1–1.2) x U
r
(0.5–2.0) x I
r
Phase angle ± 180°
Harmonic distortion 10% from 2nd – 50th
Interfering signal:
Magnitude
Minimum frequency
Maximum frequency
10% of fundamental signal
0.1 x f
r
1000 Hz
Line differential protection RED670
1MRK 505 379-BEN N
Version 2.2
Hitachi Power Grids 93
© Copyright 2017 Hitachi Power Grids. All rights reserved