PID-6193-SETTINGS v5
Table 5: RS485PROT Non group settings (basic)
Name Values (Range) Unit Step Default Description
ProtocolSel Disabled
DNP
IEC103
-
- Disabled Protocol selection
PID-3715-SETTINGS v8
Table 6: DNPGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
PID-6992-SETTINGS v1
Table 7: MSTSER Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
ChToAssociate RS485
Optical
- - RS485 Channel to associate to
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddress 0 - 65519 - 1 1 Master address
Obj1DefVar 1:BI
2:BI+Flags
- - 1:BI Object 1, default variation
Obj2DefVar 1:BIEv
2:BIEv+AbsTime
3:BIEv+RelTime
-
- 3:BIEv+RelTime Object 2, default variation
Obj3DefVar 1:DI
2:DI+Flags
- - 1:DI Object 3, default variation
Obj4DefVar 1:DIEv
2:DIEv+AbsTime
3:DIEv+RelTime
-
- 3:DIEv+RelTime Object 4, default variation
Obj10DefVar 1:BO
2:BO+Flags
- - 2:BO+Flags Object 10, default variation
Obj20DefVar 1:CNT32+Flags
2:CNT16+Flags
5:CNT32
6:CNT16
-
- 5:CNT32 Object 20, default variation
Table continues on next page