Name Values (Range) Unit Step Default Description
Obj22DefVar 1:CNTEv32
2:CNTEv16
5:CNTEv32+Time
6:CNTEv16+Time
-
- 1:CNTEv32 Object 22, default variation
Obj30DefVar 1:AI32Int+Flags
2:AI16Int+Flags
3:AI32Int
4:AI16Int
5:AI32Flt+Flags
6:AI64Flt+Flags
-
- 3:AI32Int Object 30, default variation
Obj32DefVar 1:AIEv32Int
2:AIEv16Int
3:AIEv32Int+Time
4:AIEv16Int+Time
5:AIEv32Flt
6:AIEv64Flt
7:AIEv32Flt+Time
8:AIEv64Flt+Time
- - 1:AIEv32Int Object 32, default variation
Table 8: MSTSER Non group settings (advanced)
Name Values (Range) Unit Step Default Description
ValMasterAddr No
Yes
- - Yes Validate source (master) address
AddrQueryEnbl No
Yes
- - Yes Address query enable
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No
Yes
- - Yes Enable application for multiple fragment
response
ConfMultFrag No
Yes
- - Yes Confirm each multiple fragment
UREnable No
Yes
- - Yes Unsolicited response enabled
UREvClassMask Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
- - Disabled Unsolicited response, event class mask
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line
retry mode
tVRRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tVROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay in s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
Table continues on next page
1MRK 511 391-UUS C Section 4
DNP3 parameters
670 series 2.2 ANSI 33
Communication protocol manual