Name Values (Range) Unit Step Default Description
tVREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event buffer
timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tVREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event buffer
timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tVREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event buffer
timeout
DelOldBufFull No
Yes
- - No Delete oldest event when buffer is full
ExtTimeFormat LocalTime
UTC
- - UTC External time format
DNPToSetTime No
Yes
- - Yes Allow DNP to set time in IED
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No
Yes
- - No Time synchronization request after timeout
Averag3TimeReq No
Yes
- - No Use average of 3 time requests
PairedPoint No
Yes
- - Yes Enable paired point
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
PID-4106-SETTINGS v7
Table 9: CHSEROPT Non group settings (basic)
Name
Values (Range) Unit Step Default Description
BaudRate 300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
57600 Bd
115200 Bd
- - 9600 Bd Baud-rate for serial port
Section 4 1MRK 511 391-UUS C
DNP3 parameters
34 670 series 2.2 ANSI
Communication protocol manual