1MDU07212-YN Rev. D Section 6
Installation
REF601 / REJ601 / REM601 79
Application Manual
Table 33: Binary Output configuration, continue
Binary output
Signal to
activate output
BO1
BO2
BO3
BO4
BO5
BO6
3Ith > Alm
3Ith> Blkcl
I2/I1> Str
I2> Start
Trip : I> / 51
(x)
(x)
(x)
Trip : I>> / 50-1
(x)
(x)
(x)
Trip : I>>> / 50-2
(x)
(x)
(x)
Trip : Io> / 51N
(x)
(x)
(x)
Trip : Io> / 50N
(x)
(x)
(x)
3Ith > Trip
I2/I1> Trip
I2> Trip
BF Stage1
BF Stage2
BF RecTrip
O->I Close
O->I InPro
O->I FinalTr
O->I Blocked
Signal 1
Signal 2
Signal 3
CB Open Command
(x)
(x)
CB Close Command
(x)
TCS Fault
Unit Ready
(x)
Output behavior : - = Non inverted, “I” = Inverted