Table 21. Electromagnetic compatibility tests
Description Type test value Reference
1 MHz/100 kHz burst
disturbance test:
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
Electrostatic discharge test: IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
Radio frequency interference
tests:
10 V (rms)
f=150 kHz-80 MHz
IEC 60255-22-6, class III
IEC 61000-4-6
10 V/m (rms)
f=80-2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=80-1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance
tests:
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
All ports
4kV
Surge immunity test: IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV, line-to-earth
Other ports 4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz)
magnetic field:
IEC 61000-4-8
Continuous
1-3 s
300 A/m
1000 A/m
Motor Protection and Control 1MRS756890 D