Loading...
Table 21. Electromagnetic compatibility tests, continued
Description Type test value Reference
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity
test:
Common mode
Differential mode
Binary inputs only
300 V rms
150 V rms
IEC 61000-4-16
IEC 60255-22-7, class A
Emission tests: EN 55011, class A
IEC 60255-25
Conducted
0.15-0.50 MHz < 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5-30 MHz < 73 dB(µV) quasi peak
< 60 dB(µV) average
Radiated
30-230 MHz < 40 dB(µV/m) quasi peak,
measured at 10 m distance
230-1000 MHz < 47 dB(µV/m) quasi peak,
measured at 10 m distance