EasyManua.ls Logo

ABB RELION REM615 - 3.3 Application Layer Data Mappings and Functions

ABB RELION REM615
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 22. Insulation tests
Description Type test value Reference
Dielectric tests IEC 60255-5 and
IEC 60255-27
Test voltage 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
Impulse voltage test IEC 60255-5 and
IEC 60255-27
Test voltage 5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
Insulation resistance
measurements
IEC 60255-5 and
IEC 60255-27
Isolation resistance
>100 MΏ, 500 V DC
Protective bonding
resistance
IEC 60255-27
Resistance
<0.1 Ώ, 4 A, 60 s
Table 23. Mechanical tests
Description
Reference Requirement
Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Class 2
Shock and bump test IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Class 2
Seismic test IEC 60255-21-3 Class 2
Table 24. Product safety
Description Reference
LV directive 2006/95/EC
Standard EN 60255-27 (2005)
EN 60255-1 (2009)
Motor Protection and Control 1MRS756890 D
REM615
Product version: 3.0 Issued: 2010-06-29
28 ABB