IEC 61850 name AFL-Common SA name Description DPI value FUN INF InUse ASDU GI Coding
CTRL.CCBRBRF1.OpEx.general CCBRBRF1.TRBU CBFP Failure, external trip 10=Failure,external trip 240 102 0 2 0 1
CTRL.CCBRBRF1.OpIn.general CCBRBRF1.TRRET CBFP Operate, internal retrip 10=Operate, internal re-trip 240 103 0 2 0 1
CTRL.CBCSWI1.Pos.stVal CBXCBR1.POSITION Circuit breaker position
10=Close; 01=Open;
00=Intermediate; 11=Error 240 160 1 1,20 1 2
Circuit breaker condition monitoring
LD0.SSCBR1.RsAccAPwr.ctlVal SSCBR1.RST_IPOW Reset accumulation energy 10=Reset 242 19 1 20 0 1
LD0.SSCBR1.RsCBWear.ctlVal SSCBR1.RST_CB_WEAR
Reset CB remaining life and
op.counters 10=Reset 242 20 1 20 0 1
LD0.SSCBR1.RsTrvTm.ctlVal SSCBR1.RST_TRV_T Reset CB travelling time alarm 10=Reset 242 21 1 20 0 1
LD0.SSCBR1.RsSprChaTm.ctlVal SSCBR1.RST_SPR_T Reset CB spring charge time alarm 10=Reset 242 22 1 20 0 1
LD0.SSCBR1.OpnAlm.stVal SSCBR1.TRV_T_OP_ALM Open travel time exceeded 10=Open travel time alarm 242 101 0 1 0 1
LD0.SSCBR1.ClsAlm.stVal SSCBR1.TRV_T_CL_ALM Close travel time exceeded 10=Close travel time alarm 242 102 0 1 0 1
LD0.SSCBR1.SprChaAlm.stVal SSCBR1.SPR_CHR_ALM Spring charging time exceeded 10=Spring charging time alarm 242 103 0 1 0 1
LD0.SSCBR1.OpNumAlm.stVal SSCBR1.OPR_ALM Num of CB operations alarm 10=CB operations alarm 242 104 0 1 0 1
LD0.SSCBR1.OpNumLO.stVal SSCBR1.OPR_LO Num of CB operations lockout limit 10=CB operations lockout alarm 242 105 0 1 0 1
LD0.SSCBR1.LonTmAlm.stVal SSCBR1.MON_ALM
CB 'not operated for long time'
alarm 10=CB unactive alarm 242 106 0 1 0 1
LD0.SSCBR1.PresAlm.stVal SSCBR1.PRES_ALM Pressure below alarm level 10=Low pressure alarm 242 107 0 1 0 1
LD0.SSCBR1.PresLO.stVal SSCBR1.PRES_LO Pressure below lockout level 10=Low pressure lockout alarm 242 108 0 1 0 1
LD0.SSCBR1.APwrAlm.stVal SSCBR1.IPOW_ALM Acc. currents power (Iyt),alarm limit 10=Iyt alarm 242 109 0 1 0 1
LD0.SSCBR1.APwrLO.stVal SSCBR1.IPOW_LO
Acc. currents power (Iyt),lockout
limit 10=Iyt lockout alarm 242 110 0 1 0 1
LD0.SSCBR1.CBLifAlm.stVal SSCBR1.CB_LIFE_ALM
Remaining life of CB exceeded
alarm 10=CB life alarm 242 111 0 1 0 1
Disconnector positions
CTRL.DCSXSWI1.Pos.stVal DCSXSWI1.POSITION Disconnector 1 position
10=Close; 01=Open;
00=Intermediate; 11=Error 253 1 1 1 1 2
CTRL.DCSXSWI2.Pos.stVal DCSXSWI2.POSITION Disconnector 2 position
10=Close; 01=Open;
00=Intermediate; 11=Error 253 2 1 1 1 2
CTRL.DCSXSWI3.Pos.stVal DCSXSWI3.POSITION Disconnector 3 position
10=Close; 01=Open;
00=Intermediate; 11=Error 253 3 1 1 1 2
CTRL.ESSXSWI1.Pos.stVal ESSXSWI1.POSITION Earth switch position
10=Close; 01=Open;
00=Intermediate; 11=Error 253 11 1 1 1 2
LHMI alarm LED indications
LD0.LEDGGIO1.SPCSO1.stVal - LED 1 state 10=LED ON, 01=LED OFF 253 89 1 1 1 1
LD0.LEDGGIO1.SPCSO2.stVal - LED 2 state 10=LED ON, 01=LED OFF 253 90 1 1 1 1
LD0.LEDGGIO1.SPCSO3.stVal - LED 3 state 10=LED ON, 01=LED OFF 253 91 1 1 1 1
LD0.LEDGGIO1.SPCSO4.stVal - LED 4 state 10=LED ON, 01=LED OFF 253 92 1 1 1 1
LD0.LEDGGIO1.SPCSO5.stVal - LED 5 state 10=LED ON, 01=LED OFF 253 93 1 1 1 1
LD0.LEDGGIO1.SPCSO6.stVal - LED 6 state 10=LED ON, 01=LED OFF 253 94 1 1 1 1
LD0.LEDGGIO1.SPCSO7.stVal - LED 7 state 10=LED ON, 01=LED OFF 253 95 1 1 1 1
LD0.LEDGGIO1.SPCSO8.stVal - LED 8 state 10=LED ON, 01=LED OFF 253 96 1 1 1 1
Table continues on next page
1MRS756882 B Section 2
IEC 60870-5-103 data mappings
REM615 17
Point List Manual