5 Connecting
5.1 Required tools
Table 3: Tools for connector installation
Connector type Tool for anchoring connector Tool for connecting
wire
Slotted head (DIN
5264) (mm)
ISO 8764/2 Slotted head (DIN
5364) (mm)
CT/VT connectors
Compression 0.6x3.5 0.6x3.5
Ring lug 1.0x4 1.0x4
Signal connectors
Compression PH 0, PZ 0 0.6x3.5
Ring lug PH 2 0.5x3
Push-in 0.6x3.5 0.6x3.5
IRIG-B connector
IRIG-B 0.4x2.5 0.4x2.5
5.2 Connecting wires
All connections are made on the front of the case. No soldering is needed.
1. Connect signal connector terminals.
2. Connect compression type (X1 and X2) terminals for CTs/VTs.
3. Connect the terminals on the communication module for IRIG-B.
4. Connect the RTD inputs and mA outputs using shielded stranded cables and
connect the cable shield to GND rail.
5. Connect all the sensors of the same type to adjacent channels.
The cable shield is to be earthed at only one end of the cable with RTD
cable shield rail.
Use fine wire in door mounting.
See the technical manual for product-specific terminal diagrams.
1MRS759115 E Connecting
REX640
Installation Manual
67