Table 8: IRF LED status
LED Color Decsription
Off -
Green Normal mode
Red Activated
The trip circuit supervision hardware includes constant current generator to provide
trip circuit supervision (TCS) current and TCS input that can be connected to the TCS
function with Application Configuration in PCM600. See trip circuit supervision
function TCSSCBR in the protection relay's technical manual for TCS connections.
When testing TCS connections, the TCS button needs to be pushed. The operation of
TCS can be seen on the HMI. When testing TCS, its output (PODP1, PODP2, PODP3,
SP06 or SP08) needs to be in inactive mode.
Table 9: LED status of PODP1 output and the TCS button
LED Color Decsription
PODP1
TCS
Off -
Green Activated
1. Ensure that the Test mode is activated.
2. On the Testing and Commissioning page, select Force Outputs.
3. On the Force Outputs page, force the state of digital outputs.
GUID-153062F6-F84E-4D46-8F11-55AE26783C68 V1 EN
Figure 16: Force Outputs page