Table 12:
Degree of protection of BIO-Tester Relion
®
REX640
Description Value
Closed lid IP 67
Open lid IP 20
Table 13: Environmental conditions
Description Value
Application field Indoor use
Operating temperature range +5...50°C (+41...122°F)
Transport and storage temperature range -25...+70°C (-13...+158°F)
Humidity range Maximum relative humidity 80% for temperature
up to 31°C decreasing linearly to 50% relative
humidity at 40°C
Table 14: Ratings of output connector terminals
Description Value
PSM1001/1002/
1003 connector
Rated voltage 48 or 110 VDC
Rated power Max. 100 W
BIO1001/1003
connector and
BIO1002/1004
connector
Binary inputs
Rated
voltage
12...200 VDC
Rated power Max. 15 W (200 VDC)
SW fuse ~65 mA
Binary
outputs
Rated
voltage
48 VDC
Rated power Max. 100 W
LHMI 48 VDC
connector
Rated voltage 48 VDC
Rated power Max. 100 W
Table 15: Main power switch and main's wall plug connector
Description
Value
Rated frequency 50/60 Hz
Rated voltage 100...240 VAC
Rated power Max. 230 W
Rated input current 1 A
Fuse type T2A/250 V