EasyManua.ls Logo

ABB REM 545 - External Parameterization; Storing of Parameters and Recorded Data

ABB REM 545
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
1MRS750915-MUM
Machine Terminal
Technical Reference Manual, General
REM 54_
5.1.4.2. External parameterization
The Relay Setting Tool is used for parameterizing and setting the machine terminals
externally. The parameters can be set off-line on a PC and downloaded to the
machine terminal over a communication port. The menu structure of the setting tool,
including views relating to parameterization and settings, is the same as the menu
structure of the machine terminal. The use of the tool is instructed in the RED Relay
Tool Operator’s Manual (see “Related documents” on page 10).
A060250
Fig. 5.1.4.2.-1 Main dialog window of the Relay Setting Tool
5.1.4.3. Storing of parameters and recorded data
When parameter values are changed, the new values take effect immediately.
However, the new parameter values as well as the recorded data are saved in a non-
volatile memory only after they have been stored via the parameter Store in the
menu Configuration/General (refer to the Operator’s Manual) or via the
relay tools.
Provided the storing was completed successfully, the information stored in the non-
volatile memory is preserved in the memory also in case of a power interruption.
During the storing procedure, it is not possible to reset the machine terminal via the
parameter Software reset or to load a new project.

Table of Contents