68
1MRS750915-MUM
Machine Terminal
Technical Reference Manual, General
REM 54_
The following values are recommended for the resistor Rh
ext
in refer to
chapter 5.1.11.-1 below:
A060255
Fig. 5.1.11.-1 Operating principle of the trip circuit supervision (TCS) function
5.1.11.1. Configuring the trip circuit supervision CMTCS_
The Relay Configuration Tool can be used to connect the trip circuit supervision
input status signals to the function blocks CMTCS1 and CMTCS2. The
configuration of the blocking signal is user-specific and can only be defined in the
machine terminal configuration. The trip circuit supervision inputs in the machine
terminal configuration are as follows:
TCS1 and TCS2 inputs in REM 543 and REM 545:
For more information about the trip circuit supervision functions CMTCS1 and
CMTCS2, refer to the Technical Descriptions of Functions CD-ROM.
Operating voltage Uc
Shunt resistor Rh
ext
48 V DC
1.2 k
Ω, 5 W
60 V DC
5.6 k
Ω, 5 W
110 V DC
22 k
Ω, 5 W
220 V DC
33 k
Ω, 5 W
+
U
I
Rh
R
Rh
CMTCS_
A
LARM
TCS_
BS
TCSSTATE ALARM
-
20 V
c
c
int
1 kW
ext
s
Trip Circuit Supervision 1 input PS1_4_TCS1
Trip Circuit Supervision 2 input PS1_4_TCS2