Machine Terminal
Technical Reference Manual, General
A060271
Fig. 5.1.14.-2 Menu level structure
For more detailed information about the HMI, please refer to the Operator’s Manual.
5.1.15. Alarm LED indicators
The REM 54_ machine terminal offers eight alarm LED indicators to be configured
with the Relay Mimic Editor. The LED colours are green, yellow or red, and their
use can be freely defined (for defining the ON and OFF state texts, refer to section
“MIMIC configuration” on page 35). Three basic operation modes are supported:
non-latched light
latched-steady light
latched blinking light
Alarms can be acknowledged remotely, locally or by using logic.
The alarm channels include time tagging for detected alarms. The time tagging
principle used depends on the operation mode.
0.0kV
G
CB
DC
0kW
0kVAr
0A
cos(f)0.00
IL1-A 00250.0
IL2-A 00252.0
IL3-A 00249.0
Io-A 00000.0
Iob-A 00000.0
Uo-V 000000
U1-kV 020.00
U2-kV 020.00
U3-kV 020.00
f-Hz 50.00
Demand values
IL1-A 00248.0
IL2-A 00251.0
IL3-A 00250.0
Power
P-kW 006928
Setting group 1
EVENT view
ALARM view
USER LEVEL (LEVEL 1)
TECHNICAL LEVEL (LEVEL 2)
MIMIC view MEASUREMENT view
CB spring ready
SF6 gas density
Temperature
Interlocking
PARAMETER MENU
GROUP MENU
MAIN MENU
2 Sec
1 Sec
Protection
NOC3Low
SUBGROUP MENU
Operation mode
= Definite time
Start current
= 3.1 x In
Operate time
= 041.03 s
Time multiplier
= 0.78
IEEE time dial
= 0.5
Actual setting
Setting group 1
Setting group 2
Control setting
Input data
Output data
Recorded data 1
Recorded data 2
Recorded data 3
Inrush3
MotStart
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
NPS3Low
NPS3High
NUC3St1
NUC3St2
TOL3Dev
Updating values
¬ MIMIC EVENT®
MIMIC view
¬ ALARM MEAS®
MEASUREMENT
EVENTS
NOC3Low 31/E1
2005-03-24
18:35:12.230
NOC3Low 31/E1
2005-03-24
18:35:12.330
NOC3High 32/E1
2005-03-24
14:25:52.720
NOC3High 32/E3
2005-03-24
14:25:52.760
Event list
¬ MIMIC EVENT®
C clears ALARMs
¬ EVENT MIMIC®
á , â Move cursor
E MIMIC Submenu
®
Status
Protection
Control
Cond.monit.
Measurement
Communication
General func.
Tests
Information
Configuration
MAIN MENU
á ,
â Move cursor
¬MainMenu Next®
á , â Move cursor
¬Prev. Param.®
á , â Move cursor
¬Prev. E set

Table of Contents