The disturbance recorder and load profile files in COMTRADE format are retrieved
from the \COMTRADE\ and \LPD\COMTRADE\ directories by using PCM600 or
any other client supporting IEC 61850 file transfer service or FTP.
When setting the parameter Configuration/Communication/MMSLPRT1/Unit
mode to “Primary”, the values sent over IEC 61850 are scaled according to the CT and
VT settings.Restart the protection relay after changing the parameter. This feature is
needed if the SCADA system or substation gateway does not handle scaling from
nominal values.
Section 4 1MRS757809 C
615 series data model
22 REC615 and RER615
Engineering Guide