RELION® PRODUCT FAMILY
Grid Automation
REC615 and RER615
Operation Manual

Table of Contents

Other manuals for ABB RER615

Questions and Answers

  • E
    Emily RamirezAug 10, 2025
    What to do if CMT data points are updating from Application Configuration in ABB Control Unit?
    • J
      Jeffery MartinezAug 10, 2025
      If CMT data points are updating from Application Configuration in your ABB Control Unit, it may be because when some AFLs are added to the ACT logic, the related data points are again synchronized to the Communication Management tool although the data are already in the selected list. Verify the DNP3 mapping if a new AFL has been added to the ACT logic as some signals may have disappeared.
  • A
    Anna NelsonAug 26, 2025
    How to fix slow or no update of data in ABB Control Unit?
    • M
      Marie GibsonAug 26, 2025
      If you experience slow or no data updates and disabled reports with your ABB Control Unit, manually select the check boxes for clients of all visible 61850 data sets in the IEC 61850 Configuration tool. Refer to the engineering guide for detailed instructions. This enables reporting for the data sets, and report control blocks should appear on the Report Control tab.