EasyManua.ls Logo

ABB RER615 - Page 76

ABB RER615
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GUID-5D55765D-E23A-4376-869E-331F4293422B V1 EN
Figure 43: Editing the IED capabilities
3. Edit the properties and addresses of the sampled value control block.
GUID-F5503ED3-E477-43A5-96D5-5DE1FAE6415E V1 EN
Figure 44: Sampled value control block
Some switches do not support multicast filtering with VLAN
value “0” because it means “no VLAN” and VLAN 1 has special
purpose as management VLAN for switches. Recommended
value for VLAN is 2...1001.
Use a unique multicast address for each SVCB. The address
range for sampled values multicast addresses is 01-0CCD-
04-00-00...01-0C-CD-04-FF-FF.
4. Connect the SMV sender and receivers.
Section 6 1MRS757809 C
Process bus and IEEE 1588 time synchronization
68 REC615 and RER615
Engineering Guide