1MAC306892-MB C Section 3
Vendor-specific implementation
RER620 17
Communication Protocol Manual
• Control operation is denied by the circuit breaker itself because of, for example,
interlocking.
• Remote Mode is not enabled.
3.5 Addressing scheme
3.5.1 Default addresses
There are some protection functions, which are not available in this protective relay, but
might be available in other protective relays in the 615/620 series. The main principle is to
keep the data mapped in a consistent way in the whole 615/620 series, which means that
there are some gaps in the address range. The addresses are laid in a structured form to
have a different address range for the different information object types.
3.5.2 Configuring communication options
• Configure the communication options by using LHMI or PCM600 to set the
parameters in Configuration/Communication/IEC60870-5-101/104.
• For remapping the data object use the Communication Management tool in PCM600.
3.6 Communication parameters
3.6.1 Port
• NONE (default)
• IEC101 - COM1
• IEC101 - COM2
• IEC104 - Ethernet
The setting enables/disables the protocol instance and defines the link layer.
3.6.2 ClientIP
The setting defines the IP address of the client. If the protocol instance is enabled, the
ClientIP setting must be different from other instances' ClientIPs. The meaning of the
parameter depends on the link mode.
All the parameter names have a number in the end of the caption. The
setting affects only to the protocol instance marked by the number.
Applicable for IEC 60870-5-104 only.